| Sign In | Join Free | My xxjcy.com | 
              
  | 
      
Brand Name : KSTONE
Model Number : KS200
Place of Origin : Shanghai
Price : $2000-$100000
Payment Terms : ,T/T
Packaging Details : Carton / Wooden Box
Certification : ISO9000
MOQ : 5
Supply Ability : 1000
Delivery Time : 7-10 work days
Measurement Parameters : humidity, density and temperature of SF6 gas
Dew point range : -50…+20℃ Td/f
Pressure range : 0…+10 bar
Temperature range : -40…+80℃
Calculated Parameters : Parameters converted to standard conditions at 20 °C
Micro-water value : 10…20000 ppm
Pressure value (density) : 1 ...12 bar
Dew point accuracy : ±3℃ Td
Pressure value (density) accuracy : ±0.1% FS
Temperature accuracy : ±1℃
High Precision SF6 On-line Monitor KS200 - Dew Point, Pressure, Temp, Leak Alarm, RS485, IP65 - For Outdoor Use
Main functions:
(1) On-line monitoring of the humidity, density and temperature of SF6 gas;
(2) On-line monitoring of SF6 leakage and leakage alarm;
(3) The low-pressure alarm and locking device can be automatically started according to the preset value or the value given by the user;
(4) RS-485/CAN bus communication interface is reserved;
(5) Automatically draw the state change trend chart through the background software;
(6) A large-screen liquid crystal display can be selected to display real-time data on site, with screen protection and sound-controlled display functions;
(7) Set the alarm and locking threshold values and the display mode through a handheld remote controller;
(8) It is fully sealed, anti-interference, and suitable for outdoor and low-temperature environments.
| Measurement Parameters | |
| Dew point range: | -50…+20℃ Td/f | 
| Pressure range: | 0…+10 bar | 
| Temperature range: | -40…+80℃ | 
| Calculated Parameters | Parameters converted to standard conditions at 20 °C | 
| Micro-water value: | 10…20000 ppm | 
| Pressure value (density): | 1 ...12 bar | 
| SF6 mixed density: | 0 ...100 kg/m³ | 
| Output Parameters: | 
			 PPM20 (micro-water at 20℃), P20 (pressure and density at 20℃), T (℃), Td (dew point), P (pressure), Tdatm (atmospheric dew point), density (kg/m³)  | 
		
| Accuracy | |
| Dew point accuracy: | ±3℃ Td | 
| Pressure value (density) accuracy: | ±0.1% FS | 
| Temperature accuracy: | ±1℃ | 
| Sensor Response Time | |
| Dew point sensor: | 2S (at 20℃) | 
| Pressure sensor: | <0.5S (at 20℃) | 
| Operating Environment | |
| Transmitter operating temperature: | -40...+80℃ | 
| Overload safety pressure: | 20 bar | 
| Relative humidity: | 0~100RH% | 
| Measured gas: | SF6, SF6/N2 mixed gas | 
| Output | |
| Communication method: | RS485 | 
| Communication protocol: | ModBus RTU | 
| Transmission speed: | 9600 bps | 
| General Parameters | |
| Operating voltage: | 18…36VDC | 
| Power: | <3W | 
| Weight: | 361g | 
| Protection level: | IP65 | 
| Housing material: | Stainless steel | 
| Connector material: | Stainless steel | 
| Electrical connector: | M12 connector | 
| Mechanical interface: | M301.5 | 
| Sealing method: | O-ring (332.5mm) | 
| Absolute air leakage rate: | ≤10-9Pa·m3/s (helium detection) | 
| Rated inflation pressure: | 0.6MPa abs | 
| 
                                             | 
                